GENERAL AIRSTAGE | Technical Support

Snow Falling Protection Fan Mode

How to disable the function using the outdoor unit control PCB
This procedure explains how to navigate the outdoor unit's PCB menu and disable Snow Falling Protection Fan Mode using Function 22.
Important: This is a technical configuration procedure for appropriately qualified personnel. Confirm the applicable unit and service documentation before changing operating parameters. The source guide does not specify model applicability.

Setting reference

FunctionValueSource description
22 - Snow falling protection fan mode00Valid (enabled)
01Invalid (disabled) - setting used in this procedure

Step-by-step procedure

Use the MODE/EXIT, SELECT and ENTER buttons on the outdoor unit control PCB. The displays below reproduce the sequence shown in the supplied guide.

StepActionPCB display
1Start at the normal display as illustrated in the guide.S n
2Press MODE/EXIT.F1
3Press SELECT to advance to F2.F2
4Press ENTER to access the function selection menu.00--
5Press SELECT repeatedly until function 22 is displayed.22--
6Press ENTER to open the setting. The guide shows the current setting as 00.00
7Press SELECT to change the value to 01 (disabled).01
8Press ENTER to confirm the selected value.01
Result: With Function 22 set to 01 and confirmed, Snow Falling Protection Fan Mode is set to Invalid (disabled), as identified in the original instructions.

Technical notes

  • The source identifies the function and menu sequence but does not list compatible model numbers.
  • The original guide does not specify any further exit, restart or power-cycle steps after confirming the value; follow the relevant model's service instructions if required.
  • When checking or restoring the setting, refer to the values in the setting reference table above.
General Airstage | Technical reference based on the supplied Snow Falling Protection Mode instruction sheet (page 1).